Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM01639
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/11/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE HAVE LICENSED ELECTRICAL CONTRACTOR CONTACT ME-NO FURTHER INSPECTIONS UNTIL CONTACT 2) FINISH ITEMS 2, 3 AND 4 FROM PREVIOUS INSPECTION |
|
08/09/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WEATHER PROOF RECEPTACLE COVER TO BE WEATHER OR NOT PLUGED INTO 408.6 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED 3) PLEASE SEPERATE GROUNDS FROM NEUTRALS 250.24 4) USE BREAKERS LISTED FOR USE BY MANUFACTURE 110.3 5) USE PROPER SCREWS TO SECURE PANEL COVER 6) REVISE PANEL SCHEDULE AND LABEL BREAKERS |