Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM01632
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/21/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEARWALL BLOCKING PANELS REQUIRE PD'S AT 3" ON CENTER 2) BLOCKING PANELS NOT NAILED PER 6/SD2 3) RED HEAD ANCHOR BOLTS LOOSE 4) GARAGE P-1 SHEARWALL REQUIRES ANCHOR BOLTS AT 32" ON CENTER S-1 NOTE "B" 5) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 6) ANCHOR W/C FLOOR FLANGE 7) PROVIDE POST UNDER EAST END OF MICRO ? TRUSS TO FOUNDATION 8) OK TO INSULATE |