Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/12/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 6, 8 AND 9 FROM PREVIOUS INSPECTION |
|
| 10/10/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC SERVICE PANEL REQUIRES NON WATER BOND LABEL 2) DBL LUGGING OF #12 AND #14 WIRES NOT ALLOWED IN PANEL 3) NO OTHER CIRCUITS ALLOWED ON BATH GFCI CIRCUIT 4) GAS BOND AND UFER CONNECTIONS LOOSE 5) NO ATTIC LIGHT FIXTURES BARE WIRES 6) SECURE ATTIC GAS LINE HINGE JOINT 7) KITCHEN SINK NOT CAULKED 8) MASTER BEDROOM CLOSET OUTLET MUST BE ARC FAULT PROTECTED 9) HALL TOILET REQUIRES 15" SIDE CLEARANCE ONLY 12" EXISTS |
|
| 10/07/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER LLOYD |
|
| 10/04/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |