Permit: T05CM01606

Parcel: 140383010

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/13/2005 BUILDING - FINAL Approved IVRS - Inspection :*
10/12/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 6, 8 AND 9 FROM PREVIOUS INSPECTION
10/10/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC SERVICE PANEL REQUIRES NON WATER BOND LABEL
2) DBL LUGGING OF #12 AND #14 WIRES NOT ALLOWED IN PANEL
3) NO OTHER CIRCUITS ALLOWED ON BATH GFCI CIRCUIT
4) GAS BOND AND UFER CONNECTIONS LOOSE
5) NO ATTIC LIGHT FIXTURES BARE WIRES
6) SECURE ATTIC GAS LINE HINGE JOINT
7) KITCHEN SINK NOT CAULKED
8) MASTER BEDROOM CLOSET OUTLET MUST BE ARC FAULT PROTECTED
9) HALL TOILET REQUIRES 15" SIDE CLEARANCE ONLY 12" EXISTS
10/07/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER LLOYD
10/04/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*