Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/08/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER JERRY |
|
| 07/14/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEARWALL 7 ANCHOR BOLTS NOT PER PLAN 2) PROVIDE EXPANSION BOLT INTALLATION STANDARDS 3) NO DWV WATER TEST |
|
| 07/13/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AB'S REQUIRED AT SW7 2) REPAIR STUDS AT DEN ABOVE DOOR |
|
| 07/06/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STUCCO MESH REQUIRES 1/4" CLEARANCE AT POP OUT COR? 2) NO DWV WATER TEST. 3) NAIL PROTECT PEX AT WATER HEATER, FRIG, THROUGHOUT 4) NAIL PROTECT WIRES THROUGHOUT. 5) FIRE BLOCK MISSING MASTER TOILET. 6) FIRE BLOCK M. BR ARCH. 7) FIRE BLOCK REQUIRES TWO LAYERS OF 1/2" O.S.B. 8) RED HEAD ANCHOR BOLTS LOOSE. 9) SHEAR WALL 7 REQUIRES 5/8" ANCHOR BOLTS AT 24" O.C |