Permit: T05CM01606

Parcel: 140383010

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/12/2005 FRAMING Approved IVRS - Inspection :*
08/08/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER JERRY
07/14/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEARWALL 7 ANCHOR BOLTS NOT PER PLAN
2) PROVIDE EXPANSION BOLT INTALLATION STANDARDS
3) NO DWV WATER TEST
07/13/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AB'S REQUIRED AT SW7
2) REPAIR STUDS AT DEN ABOVE DOOR
07/06/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) STUCCO MESH REQUIRES 1/4" CLEARANCE AT POP OUT COR? 2) NO DWV WATER TEST. 3) NAIL PROTECT PEX AT WATER HEATER, FRIG, THROUGHOUT 4) NAIL PROTECT WIRES THROUGHOUT. 5) FIRE BLOCK MISSING MASTER TOILET. 6) FIRE BLOCK M. BR ARCH. 7) FIRE BLOCK REQUIRES TWO LAYERS OF 1/2" O.S.B. 8) RED HEAD ANCHOR BOLTS LOOSE. 9) SHEAR WALL 7 REQUIRES 5/8" ANCHOR BOLTS AT 24" O.C