Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXIT LIGHT ABOVE SOUTH DOOR MISSING 2) EMERGENCY LIGHT IN CEILING ABOVE SOUTH DOOR. COVER TO BALLAST NOT INSTALLED CORRECTLY-WIRES EXPOSED 3) DO NOT SEE EMERGENCY FIXTURES AS NOTED ON PLAN CIRCUIT 7 INSTALLED 4) WILL NEED TO HAVE ELECTRICIAN OPEN SWITCH GEAR TO INSPECT TAPS 5) NEED ROOF ACCESS |
|
| 07/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* |