Permit: T05CM01590

Parcel: 13315320C


Addresses:

2130 N KOLB RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/28/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
CONNECTION TO DRAIN IS OK
08/29/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- OK TO COVER SEWER PIPE
- OK TO COVER WATER PIPE
- PROVIDE TEST ON DRAIN CONNECTION ABS CEMENTED INTO CONCRETE TANK.
08/28/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 55 PSI ON WATER OK
- CORRECT SLOPE AT VENT RISER AND ON SEWER PIPING 10'-20' S OF INTERCEPTOR.
- PROVIDE WATER TEST ON SEWER
- PROVIDE SHADING ON PIPING FROM DRAIN TO INTERCEPTORS.
- TYPE OF INTERCEPTOR & DRAIN OK
08/09/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE DOCUMENTATION ALLOWING THE TYPE OF DRAIN AND INTERCEPTOR USED IS OK, BECAUSE THE ONES INSTALLED ARE DIFFERENT THAN SPECIFIED.
- ALL NON-METALLIC PIPING BELOW GRADE REQUIRES
- TRACER WIRES OF THE APPROPRIATE COLOR
- INSTALL BLUE 18 GAUGE TRACER WIRE ON WATER, SECURE AT EVERY 8' AND AT 12" ABOVE GRADE.
- USE APPROPRIATE FITTINGS TO MAKE 45 DEG. CHANGE OF DIRECTION, PROVIDE PRESSURE GAUGE FOR TEST.
- INSTALL GREEN TRACER WIRE ON DRAIN PIPING, SECURE AT 8' INTERVALS AND TERMINATE WIRE IN CLEANOUT COVERS.
- LEAVE A MESSAGE W/YOUR PHONE # WHEN MAKING INSPECTION REQUEST SO I CAN LET YOU KNOW WHEN I AM COMING SO THAT YOU CAN REMOVE PLATES FOR INSPECTION.
- EXPOSED PIPING ON WALL SHALL BE CAST IRON AND VENT SHALL TERMINATE 6" ABOVE SIDE WALL.
- POINT OF VENT SHALL BE ABOVE THE FLOW LINE OF SEWER
- ROLL VENT FITTING UP TO A MINIMUM OF 45 DEG. TO MEET CODE.
- HAVE ELECTRICAL INSPECTION ADDED TO PERMIT CARD
CALL 791-5550 EXT. 1158