Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/13/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CORRECTLY LABEL BREAKERS 2. SUPPORT CONDUIT WITHIN 3' OF PANEL 3. ONLY ONE NEUTRAL TERMINATION TO A LUG. |