Permit: T05CM01573

Parcel: 140383840

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/14/2005 FRAMING Approved
07/27/2005 FRAMING Partial Approval IVRS - Inspection :*
1. HAVE SLAB CUT ENGINEERING APPROVED BY CITY - OK TO CONTINUE
07/26/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
2) PEX CANNOT BE WITHIN 6" OF WATER HEATER B-VENT
3) CONDUIT TO SHALLOW
4) NAIL PROTECT KITCHEN D.W.V.
5) HAVE SLAB ENGINEERING ARPPOVED BY CITY OF TUCSON
07/22/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) PROVIDE CITY OF TUCSON APPROVAL FOR THIS ADDRESS OF ENGINEERING LETTER DATED 7/20/05
2) PLASTIC ELECTRIC CONDUIT MUST BE ENCASED IN 2" OF CONCRETE-COVER TO SHALLOW
3) NO DWV WATER TEST
4) RED HEAD ANCHOR BOLTS LOOSE
5) STOPPED INSPECTION-TO MANY ITEMS
07/20/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST TENSION SLAB CUT/DAMAGED AT ISLAND CONDUIT. PROVIDE CITY OF TUCSON AND POST TENSION ENGINEER APPROVED REPAIR-DO NOT COVER
2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE
3) SHIM HEADERS TO TOP PLATES
4) PEX CANNOT BE WITH ?
5) CAN LIGHTS REQUIRE 1/2" TO COMBUSTIBLES
6) LAV DIRTY ARIM CANNOT EXCEED 1 1/2" DIAMETER 42" LENGTH
7) CRIPPLE STUDS TO SHORT THROUGHOUT
8) FIRE STOPS MISSING THROUGHOUT
9) GAS LINE CANNOT BE MORE THAN 36" FROM FURNACE CONNECTION
10) STOPPED INSPECTION-TO MANY ITEMS
2)