Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2005 | FRAMING | Approved | ||
| 07/27/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1. HAVE SLAB CUT ENGINEERING APPROVED BY CITY - OK TO CONTINUE |
|
| 07/26/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 2) PEX CANNOT BE WITHIN 6" OF WATER HEATER B-VENT 3) CONDUIT TO SHALLOW 4) NAIL PROTECT KITCHEN D.W.V. 5) HAVE SLAB ENGINEERING ARPPOVED BY CITY OF TUCSON |
|
| 07/22/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) PROVIDE CITY OF TUCSON APPROVAL FOR THIS ADDRESS OF ENGINEERING LETTER DATED 7/20/05 2) PLASTIC ELECTRIC CONDUIT MUST BE ENCASED IN 2" OF CONCRETE-COVER TO SHALLOW 3) NO DWV WATER TEST 4) RED HEAD ANCHOR BOLTS LOOSE 5) STOPPED INSPECTION-TO MANY ITEMS |
|
| 07/20/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST TENSION SLAB CUT/DAMAGED AT ISLAND CONDUIT. PROVIDE CITY OF TUCSON AND POST TENSION ENGINEER APPROVED REPAIR-DO NOT COVER 2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE 3) SHIM HEADERS TO TOP PLATES 4) PEX CANNOT BE WITH ? 5) CAN LIGHTS REQUIRE 1/2" TO COMBUSTIBLES 6) LAV DIRTY ARIM CANNOT EXCEED 1 1/2" DIAMETER 42" LENGTH 7) CRIPPLE STUDS TO SHORT THROUGHOUT 8) FIRE STOPS MISSING THROUGHOUT 9) GAS LINE CANNOT BE MORE THAN 36" FROM FURNACE CONNECTION 10) STOPPED INSPECTION-TO MANY ITEMS 2) |