Permit: T05CM01570

Parcel: 12005275A


Addresses:

4654 S 16TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05CM01570

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1ST FLOOR EAST END OK FOR TILES
P-TAC UNITS ON FINAL
FIRE CAULK AT DAMPERS ON FINAL
12/13/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CAULK LINE AT F.S DAMPERS
PROVIDE PROPER STRAPPING ON FLEX DUCT

CAC/DBP IS THIS CARRIER - KFCEH?
12/10/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/27/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/07/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1 & 2 FLOORS
10/31/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR ELEVATOR LOBBY PROVIDE SPACE FOR FIRE-RATED ACCESS DOOR AT FIRE DAMPER. PROPERLY INSTALL F.D FLANGES. PROVIDE ACCESS TO ALL FIRE DAMPER FUSABLE LINKS.
10/12/2007 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/09/2007 MECHANICAL - INTERMEDIATE Not ready for Inspection MATT INSPECTED APPROX 1 PM
10/09/2007 MECHANICAL - INTERMEDIATE Partial Approval OK ROCK EXCEPT FOR TRASH ROOM
PROVIDE 10" AT E.F
10/08/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
NO B.D DAMPER ON E.F IN ELEC. ROOM
NEED STRAPS ON E.F DUCT
DOVE TAILS NOT FASTENED AT FIRE DAMPERS

OK TO ROCK ALL BUT BEAUTY SHOP & ELEC ROOM (EF-4)
09/10/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE SECONDARY DRAINS OR CORRIDOR FAN COILS
OK SHEETROCK PHASE III
08/30/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
EXHAUST MISSING IN MANAGERS UNIT 1ST FLOOR
OK FOR SHEETROCK 1ST & 2ND FLOOR PHASE 2
APTS. ONLY
08/22/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK 1ST & 2ND FLOOR PHASE 1 APTS
08/20/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE SCREWS IN ALL JOINTS OF EXHAUST DUCT
2) DO A BETTER JOB TAPING JOINTS