Permit: T05CM01570

Parcel: 12005275A


Addresses:

4654 S 16TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM01570

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
COURTESY
10/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK ROUGH INTO PANELS FOR LIGHTING & POWER FOR COMMON AREAS
- OK MULTIMETER PACK 3RD PHASE
- OK ROUGH CLUBHOUSE, KITCHEN AREAS
09/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH FOR PHASE 3
09/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK POLE BASES
08/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH PHASE 2
08/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WATER HTR POWER ROUGH IN WALLS
08/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS, CEILINGS, PHASE 1ST & 2ND FLOOR
SUBJECT TO LETTER FROM ARCH. PER LAST INSP. NOTES
07/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLANS CALL OUT #3 FEEDERS IN CONDUIT TO UNITS
COPPER OR ALUM. CONDUCTORS NOT SPECIFIED,
CONTR. INSTALLED #1 ALUM PROVIDE LETTER STAMPED BY ARCH. FOR APPROVAL OF THIS CHANGE. ADDRESS COPPER OR ALUM.

ELECTRIC ROUGH APPROVAL SUBJECT TO LETTER FROM ARCH. FOR PANEL FEEDERS, LOW VOLTAGE/DATA CABLING
NOT INSTALLED YET