Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
Permit Number - T05CM01570
Inspection Description - SHEET ROCK NAILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2008 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
12/17/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* REPAIR ELEV. SHAFT WHERE SCAFFOLD REMOVED |
|
11/27/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* | |
10/16/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1. ALL BUT 1ST FLOOR LAUNDRY, ELEV. LOBBY, TRASH ROOM 2. ABOVE CEILING FIRESTOP IN CORRIDORS INCOMPLETE 3. UEU305 IS 1 HOUR WALL FOR CORRIDORS BASICALLY WOOD FRAME WITH GYPSUM ON BOTH SIDES - DEFINITION OF FIRE BARRIER REQUIRES THEY EXTEND FROM FLOOR BELOW TO DECK ABOVE THEREFORE GYPSUM IS REQUIRED ON BOTH SIDE OF CORRIDOR WALLS FLOOR TO DECK. IT MAY NOT TERMINATED ON ONE SIDE AT CEILING. |
|
10/09/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* WITHOUT ARCHITECT DETAILING CORRIDOR ASSEMBLY UL U305 THEN A CORRIDOR MUST HAVE WALL TO ECK NOT CEILING CHECK SEC U305 L528 SYSTEM 4 |
|
10/01/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR PHASE 2 |
|
09/24/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 2ND FLOOR GUESTROOMS OK PHASE 1, 2, 3 2ND FLOOR CORRIDOR EXCEPT PHASE 3 OK N/WEST STAIR OK N/EAST STAIR OK |
|
09/18/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1. 1ST FLOOR PHASE 1 - GUESTROOMS FIRESTOP OK 2. 1ST FLOOR PHASE 2 WEST END OK |
|
09/17/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* | |
09/13/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 2ND FLOOR 2ND PHASE; 1 NEED TO SEE FIRE STOP BEFORE TAPING AROUND PENETRATIONS |
|
09/11/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR 1ST PHASE/2ND FLOOR 2ND PHASE RECALL BEFORE TAPING |
|
09/05/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 2ND FLOOR DWELLING UNITS OK EXCEPT DO NOT TAPE FIREWALL PENETRATIONS. |
|
08/31/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* PROGRESS OK -- CALL WHEN FLOOR DONE |
|
08/28/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1ST LAYER LIDS & 2ND FLOOR OK WEST WING |
|
08/10/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1) PHASE 3 1ST LAYER LIDS 1ST AND 2ND FLOOR |
|
08/01/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* FIRST LAYER OF DRYWALL INSTALLATION ON FIRST AND SECOND LEVEL FLOOR PHASE 2 ON CORRIDOR. |
|
07/26/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS THE FOLLOWING AREAS 1ST FLOOR LEVEL PHASE I SECOND LAYER, 2ND FLOOR LEVEL FIRST LAYER |
|
07/24/2007 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS NAILING FIRST LAYER OF FIRE RESISTANT PROTECTION ON CORRIDOR PHASE 2 |