Permit: T05CM01569

Parcel: 13316021C


Addresses:

6616 E GRANT RD


Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM01569

Inspection Description - MECHANICAL - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
02/03/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
02/03/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) AS PER OWNER, DUCT HEATER WILL NOT BE INSTALLED
2) MAKE UP AIR VENTS HAVE BEEN REPOSITIONED SO AS NOT TO CAUSE DISCOMFORT
3) OK FOR FINAL C OF O
01/27/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE MIN 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTION. PROVIDE MIN 1" CLEARANCE FROM COMBUSTIBLES AT ROOF PENETRATION. PROVIDE CONDENSATE DRAINS TO AN APPROVAL LOCATION. EXTEND SEWER VENTS 2' ABOVE EVAP. COOLERS IF WITHIN 10' EXTEND WATER HEATER VENT 2' ABOVE WALL ON ROOF.
PROVIDE ROOF JACKS ON ALL ROOF PENETRATIONS
ELEC. DISCONNECTS BLOCKING ACCESS PANELS ON CONDENSORS. PROVIDE GREASE CUPS ON EXHAUST FANS