Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM01569
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) DWV WATER TEST IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) GAS PRESSURE TEST ON ROOF ONLY IS OK 4) ALL CORRECTIONS HAVE BEEN MADE |
|
08/15/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE A WATER TEST ON DWV SYSTEM AS REQUESTED ON 6/20/05 ALL THE WAY TO TOP OF ROOF 2) SHALL PROVIDE A HANGER AT ALL HORIZONTAL VENTS THRU ROOF 3) SHALL PROVIDE REQUIRED GAS GAUAGE FOR GAS TEST |
|
06/22/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SEE NOTE #1 FROM 6/20/05 INSPECTION 2) GREASE WASTE INSTALLED PER RED LINE DRAWING ON SITE. CONTRACTOR WILL SUPPLY LISTING FOR 2" INLET AND 4" OUTLET ON 4" GREAS TRAP. COVER AT OWN RISK. WATER TEST IS OK 3) HAVE 3050 YARD WATER ADDED WITH 3005 INSPECTION TO YOUR PERMIT CARD 4) 3040-1 1/4 YARD WATER FROM METER THRU BACKFLOW DEVICE INTO BLDG (PARTIAL APPROVAL) 3/4 METER IS ISNTALLED NOW, 1" METER MAY BE INSTALLED AT LATER DATE IF SO WILL NEED TO VIEW CONNECTION |