Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. APPROVED EXTENDER RING NEEDED FOR BOXES MORE THAN 1/4" AT NON COMBUSTIBLES -- 314.20 2. SUPPORT BOXES ON ROOF AND TIGHTEN FITTINGS. 3. NEED MAINTENANCE RECEPTACLES ON ROOF 4. GROUNDED CONDUCTOR NOT FOR GROUNDING CONDUCTOR 5. LABEL A/C UNITS DISCONNECTS 6. BOND JUNCTION BOX ENCLOSURE 7. PLEASE LABEL PANELS ON OUTSIDE COVER AND FINISH CIRCUIT DIRECTORIES 8. EM LIGHTING TO BE AS 300.12 9. FINISH SERVICE |