Permit: T05CM01569

Parcel: 13316021C


Addresses:

6616 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. APPROVED EXTENDER RING NEEDED FOR BOXES MORE THAN 1/4" AT NON COMBUSTIBLES -- 314.20
2. SUPPORT BOXES ON ROOF AND TIGHTEN FITTINGS.
3. NEED MAINTENANCE RECEPTACLES ON ROOF
4. GROUNDED CONDUCTOR NOT FOR GROUNDING CONDUCTOR
5. LABEL A/C UNITS DISCONNECTS
6. BOND JUNCTION BOX ENCLOSURE
7. PLEASE LABEL PANELS ON OUTSIDE COVER AND FINISH CIRCUIT DIRECTORIES
8. EM LIGHTING TO BE AS 300.12
9. FINISH SERVICE