Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM01554
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL WILL CHECK DUCT SMOKE DETECTORS ON T.I |
|
12/11/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* NO CONTRACTOR ON SITE |
|
12/04/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PROVIDE DUCT SMOKE DETECTORS AS PER PLANS - MARK UNIT DATA PLATE W/PROPER HEAT STRIP & FUSE ACCORDINGLY. - IDENTIFY A/C UNITS - CONNECT CONDENSATE DRAINS - BE SURE TO PROVIDE AUDIBLE & VISIBLE ALARMS IN SUPERVISED LOCATION. - CONDENSATE HOSE CONNECTORS KINKED. |