Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2006 | ELECTRIC - UFER | Approved | ||
| 11/01/2006 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1. ARCH. OF RECORD TO APPROVED USE OF ALUM. CONDUCTORS & SIZES USED AT FIELD INSTALLATIONS. PROVIDE LETTER, ALSO USE OF GROUND RODS IN LIEU OF UFER IN FOOTING. 2. VERIFY RATING OF LUGS PANEL LISTING INFO CALLS FOR 60-75 DEG. MAX AT HOUSE PANEL TERMINATION MUST BE SAME AS WIRE USED FOR AMPACITY. IF NOT, USE PROPER SIZE FEEDER CONDUCTOR. 3. COMPLETE GROUNDING IN SES 4. PROVIDE LETTER OF TORQUE FROM CONTRACTOR FOR SES 5. METAL PIPING BOND WIRE TO SMALL, USE SIZE PER PLAN 2/0 6. OK 2 GROUND RODS. |
|
| 09/28/2006 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* OK POLE BASE UFERS |