Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2005 | ELECTRIC - INTERMEDIATE | Approved | PER FINAL | |
| 05/27/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* / 1) FILL UNUSED OPENINGS IN PANEL. HOW ARE CIRCUITS TO ENTER PANEL. OK WALLS EXCEPT PANEL | |
| 05/25/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 10 FLOOR BOXES 2) FINISH #2 AND 7 FROM PREVIOUS INSPECTION |
|
| 05/20/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROTECT M/C AND PVC AT TOP AND BOTTOM PLATES 2) SUPPORT VDV CABLEING IN STUDS AND PROTECT FROM SHARP METAL EDGES. SPLICES TO BE ACCESSIBLE 3) SUPPORT PVC ON HORIZONTAL RUN 4) EXISTING RECEPTACLES IN PATIENT CARE AREAS TO COMPLY WITH 517.13 5) PLEASE CALL AND ADD 02010 TO PERMIT FOR UNDERGROUND ELECTRIC 6) FINISH PANEL WALL 7) OK WALLS ROOMS 1-9 EXCEPT AS NOTED |