Permit: T05CM01543

Parcel: 140294760


Addresses:

3892 E SUN VIEW CT

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/07/2005 FRAMING Approved IVRS - Inspection :*
1) 00035 APPROVED BY F. GREER ON 6/27/05
06/24/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) GARAGE P-1 SHEARWALL REQUIRES HILTI PINS AT 8" ON CENTER PER SHEET SL1
2) 1" CLEARANCE REQUIRED FROM WATER HEATER "B" VENT TO COMBUSTIBLE
3) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
4) A35 CLIPS AT GARGE P-1 MUST BE CLIPPED TO TRUSS NOT TO NAILER
5) PEX PLUMBING NOT ALLOWED WITHIN 12" OF RECESSED LIGHTS
6) STOPPED INSPECTION-TO MANY ITEMS