Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE TO AN APPROVABLE LEVEL 2) PLUMBING FINAL OK 3) OK FOR C OF O PENDING ANY OTHER INSPECTION |
|
| 08/24/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INDIRECT WASTE OVER FIFTEEN FEET SHALL BE SEPERATELY VENTED TO THE OUTSIDE-AND MUST BE GRAVITY DRAIN-NO BACK PITCH PERMITTED AND SHALL HAVE CLEANOUTS AT CHANGES OF DIRECTION 2) MAKE ALL CONNECTIONS, HOOK UP ALL EQUIPMENT |
|
| 08/22/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HAVE PLUMBER COMPLETE PUNCH LIST BEFORE CALLING FINAL |
|
| 08/10/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) LEFT GAS CARD |