Date Description Inspector Results Comments
07/11/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :* STUDIO 1 & 2 & CASHWARP ( REAR) NOTE *OK TO KO SEALS & GROUNDING BUS AT J-BOX
07/07/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) PROPERLY BOND JUNCTION BOX-SHEET METAL SCREWS NOT ALLOWED. ALL STRANDS UNDER TERMINATIONS 250.8, 110.12. 2) FILL UNUSED OPENINGS 110.12. 3) SUPPORT M/C CABLE WITHIN 12" OF BOXES. 4) MISSING EXTENSION RINGS. 5) BOXES MORE THAN 1/4'' FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 6) JUNCTION BOXES TO BE ACCESSIBLE. OK WALLS STUDIO #2