Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2005 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* STUDIO 1 & 2 & CASHWARP ( REAR) NOTE *OK TO KO SEALS & GROUNDING BUS AT J-BOX |
| 07/07/2005 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* 1) PROPERLY BOND JUNCTION BOX-SHEET METAL SCREWS NOT ALLOWED. ALL STRANDS UNDER TERMINATIONS 250.8, 110.12. 2) FILL UNUSED OPENINGS 110.12. 3) SUPPORT M/C CABLE WITHIN 12" OF BOXES. 4) MISSING EXTENSION RINGS. 5) BOXES MORE THAN 1/4'' FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 6) JUNCTION BOXES TO BE ACCESSIBLE. OK WALLS STUDIO #2 |