Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM01519
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE |
|
06/06/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AC UNITS OVERFUSED LABEL MISSING ON AC 1 PERMANENTLY ID EQUIPMENT ON ROOF OUTSIDE AIR QUANTITIES NOT PER PLAN AC 2 EXCEEDS 2,000 CFM FIRE DAMPER @ WOMENS RESTROOM NOT OPERATING |