Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
| 02/15/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE ANGLE IRON FRAMES AROUND DAMPERS IN RESTROOM WALLS. PROVIDE ACCESS TO DAMPER IN SOFFIT FINISH DAMPER IN ELEC. ROOM SUSPENDED ROUGH DUCT OK TO PROCEED WITH GRID |
|
| 02/12/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED PROVIDE APPROVED PLANS & INSTALL INSTRUCTIONS FOR FIRE DAMPERS. |
|
| 10/30/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSTALL DAMPERS PER INSTALL INSTRUCTIONS PROVIDE A FRAMED OPENING FOR EACH DAMPER & LINE ALL WOOD FRAMED OPENINGS WITH MIN. 1/2" FIRE-RATED SHEETROCK. PROVIDE ACCESS DOORS AS NEEDED. OK TO SHEETROCK HARD LIDS |