06/18/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED BACTERIA REPORT FOR POTABLE WATER SYSTEM |
|
05/28/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TERMINATE EXTERIOR CLEANOUTS TO GRADE WITH APPROVED GAS TIGHT CAPS 2. COMPLETE INSULATION ON ALL HOT WATER PIPING 3. MAKE ALL FIXTURES WATER TIGHT AT WALLS & FLOORS 4. PROVIDE A MEANS TO CONTROL HOT WATER TEMPERATURE AT PUBLIC USE LAVS NOT TO EXCEED 110 DEG. BESIDES THE WATER HEATER 5. ALL CLEANOUTS & FLOOR DRAINS TO BE FLUSH WITH FINISH FLOOR 6. SEPTIC ACCESS MANHOLE COVERS TO BE TO FINISH GRADE BACTERIA REPORT ON SITE |
|
02/29/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CLOSET FLANGES OK |