Permit: T05CM01519

Parcel: 13609016A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM01519

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/15/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST THRU ROOF PARTIAL APPROVAL DWV EXCEPT GANG RESTROOMS, REQUIRE PER PLAN 3" VENTING OVERHEAD FOR WOMENS AND CORRECT DIRECTIONAL VENT FITTING (DOUBLE ELL) OK 2 SEPARATE FITTINGS.
SUPPORT OVERHEAD HORIZONTAL AT 6' INTERVALS AND CHANGES OF ELEVATION & DIRECTION. WATER PIPING FROM STUB OUT OF BUILDING THRU BUILDING OK
SHALL INSULATE HOT & HOT RETURN PIPING BEFORE COVERING