Permit: T05CM01519

Parcel: 13609016A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM01519

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED LETTER OF TORQUE/NEED REVISED PLAN
2. AC-1 MISSING LISTING LABEL & MANUFACTURERS LABEL
3. NEED PROPER SIZE GROUND FOR AC UNITS
4. TERMINATE GROUNDS IN AC DISCONNECTS PROPERLY
5. MARK SERVICE DISCONNECTS FOR PANELS & BUILDINGS SERVED
6. MARK AC UNITS HOME PLATE FOR PROPER CIRCUIT AND OVER CURRENT SIZING
7. CONNECT ALL GROUNDS TO LIGHT POLES