Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T05CM01519
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
06/04/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 3/0 FOR UFER |
|
03/29/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) ELECTRIC CONTRACTOR TO PROVIDE LETTER OF TORQUE FOR TERMINATION 2) NOTE: PRIOR TO ENERGIZING NEW BLDG NEED TO POST BOND FOR TEMP POWER FOR TEST 3) CHECK FOR LISTING INSTRUCTION FOR MAIN SW ? AND 800 AMP DISCONNECT |
|
03/21/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* MEETING TO DISCUSS PROJECT |
|
03/06/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 2 - 4" PVC CONDUITS SES TO 2ND SERVICE |
|
03/02/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 4 - 4" PVC TEP TO SES OK 3 - 2 1/2" PVC SES TO SUB-PANELS OK 2 - 4" PVC 90 DEG. UNDER SES - WAVECORE NOT A LISTED PRODUCT USE LISTED MATERIAL 110.3 |
|
03/01/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* |