Permit: T05CM01485

Parcel: 140377200


Addresses:

6880 S MARTLET DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/01/2005 FRAMING Approved IVRS - Inspection :*
07/29/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE SHEARWALL REQUIRES 10 A35 CLIPS
2) INTERIOR BEARING WALL MISSING
3) RED HEAD ANCHOR BOLTS LOOSE
4) KITCHEN 1 1/2" DIRTY ARM TO LONG
5) REPLACE SHORT ?? STUD SOUTH WALL ALSO OVERNOTCHED
6) REMOVE WIRES FROM ATTIC ROOMS
7) REPLACE ALL SHORT STUDS