Permit: T05CM01482

Parcel: 14115008T


Addresses:

8120 S HOUGHTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM01482

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
AIR BALANCE REPORT OK
TESTED DUCT SMOKE DETECTORS
OK FOR FINAL
04/30/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. DUCT SMOKE DETECTOR IN KITCHEN NOT SHUTTING
OFF AC FAN
2. NEED AIR BALANCE REPORT
3. EVERYTHING ELSE OK

OK TO FILE FOR TEMP C OF O
04/27/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
ICE MACHINE CONDENSORS REQUIRE DISCONNECTS
ELEC. INSPECTOR WILL INSPECT
NEED TO TEST DUCT SMOKE DETECTOR
NEED AIR BALANCE REPORT