Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T05CM01482
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2007 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 03/29/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED FIRE WRAP OK FOR CEILING TILES TYPE 1 EXHAUST MUST TERMINATE AS PER SECTION 506.5.5 2003 IMC |
|
| 03/16/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
| 03/13/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCTS OK TO FIRE WRAP EXTEND WRAP ALL THE WAY TO TOP OF DUCT |