Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T05CM01482
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE |
|
| 04/17/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LETTER OF TORQUE 2. PROTECT #4 & LARGER CONDUCTORS PER NEC 352.46 & 300.4 3. NEED TO BOND WATER, GAS & SPRINKLER PER NEC 250.104 4. PROTECT WIRES AT SWITCH GEAR. CONDUCTORS UP AGAINST SHARP EDGES. |