Permit: T05CM01482

Parcel: 14115008T


Addresses:

8120 S HOUGHTON RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/01/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SOFFIT ABOVE COUNTER

1. SUPPORT M/C 12" FROM CANS
02/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS SUBJECT TO M/C LETTER

1. NO MORE THAN 360 DEGREES IN CONDUIT RUNS
2. PRODUCT PVC AT BASE PLATES
3. WE HAVE BOX OVERFILL
4. PLEASE PROVIDE A LETTER AUTHORIZING MC CABLE
5. SUPPORT CONDUIT 3' FROM BOXES
02/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOF RECEPTS ROUGH