Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM01461
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/05/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 12 PSI AIR TEST FROM METER AREA TO (4) HANGING HEATERS OK. PENDING VERIFICATION OF APPROVED GAS SHUT OFF VALVES. | |
| 09/30/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*PROVIDE PIPING & VALVING MEETING REQUIREMENTS OF 94 UPC TABLE 12-3 FOR 200,000 BTU DEVICE. PROVIDE FLEX LISTED FOR THIS REQUIREMENTS HARD PIPE. PROVIDE RETEST OF GAS SYSTEM IF PIPING IS CHANGED |
|
| 09/23/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE MECHANICAL INSPECTION ADDED TO PERMIT AND PROVIDE PROOF OF INSPECTION. PROVIDE BONDING OF BUILDING GAS PIPING |