Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 10/25/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR POWER, SUBJECT TO BOND POSTING AND PERMIT VERIFICATION 2) INSTALL GFI RECEPTS FOR CONST PERSONAL TO USE FOR T.I. |
|
| 10/19/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BONDING AT SERVICE OK POWER RELEASE FOR TEMP, SUBJECT TO BOND POSTING FOR TESTING. |
|
| 10/16/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BOND BUSHINGS OR LOCKNUTS, HUBS REQUIRED AHEAD OF OVERCURRENT PROTECTION. NIPPLES TO BE INSTALLED PROPERLY & BONDED ONE END AHEAD OF OVERCURRENT. 2. J-BOX MUST BE ACCESSIBLE & SUPPORTED IN AN APPROVED MANNER. 3. BUBBLE COVERS REQUIRED OUTSIDE RECEPTS. |
|
| 10/12/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. J-BOXES BEHIND WALL PACKS OUTSIDE NOT 3R RATED 2. USE LISTED OR APPROVED METHOD TO SUPPORT J-BOXES IN CEILING 1/2" FLAT STOCK OR ANGLE NOT APPROVED AS INSTALLED. |