Permit: T05CM01453

Parcel: 14027040B


Addresses:

2651 E GANLEY RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/07/2006 ELECTRIC - INTERMEDIATE Approved
10/25/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO CLEAR POWER, SUBJECT TO BOND POSTING AND PERMIT VERIFICATION
2) INSTALL GFI RECEPTS FOR CONST PERSONAL TO USE FOR T.I.
10/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BONDING AT SERVICE OK
POWER RELEASE FOR TEMP, SUBJECT TO BOND
POSTING FOR TESTING.
10/16/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BOND BUSHINGS OR LOCKNUTS, HUBS REQUIRED AHEAD OF OVERCURRENT PROTECTION. NIPPLES TO BE INSTALLED PROPERLY & BONDED ONE END AHEAD OF OVERCURRENT.
2. J-BOX MUST BE ACCESSIBLE & SUPPORTED IN AN APPROVED MANNER.
3. BUBBLE COVERS REQUIRED OUTSIDE RECEPTS.
10/12/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. J-BOXES BEHIND WALL PACKS OUTSIDE NOT 3R RATED
2. USE LISTED OR APPROVED METHOD TO SUPPORT J-BOXES IN CEILING 1/2" FLAT STOCK OR ANGLE NOT APPROVED AS INSTALLED.