Permit: T05CM01435
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/09/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) ELECTRICAL WIRES THROUGH ATTIC ACCESS 2) NO TEST ON DWV'S |
|
| 10/03/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) F7-FLOOR TRUSS NOT BEARING PER CALC'S 2) PROVIDE APPROVED TRUSS REVISION 3) NAIL PROTECT ELECTRIC WITHIN 1 1/4" FROM EDGE OF STUD 4) SEAL AROUND NESCO POPOUTS, LATH 5) REPAIR DBL TOP PLATE IN KITCHEN 6) FIREBLOCK STRINGER 7) STOPPED INSPECTION. HAVE SUPER WALK HOUSE |
|
| 09/15/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING AB ON E GARAGE WALL 2) RETRO HD @ GARAGE SHEER 3) TIGHTEN AB THROUGHOUT 4) NEED DWV TEST 5) OVERSPAN W. LIVING ROOM WALL 6) FIRESTOP SECOND FLOOR PENETRATIONS 7) NAIL PROTECTION THROUGHOUT 8) REPLACE KITCHEN OUTLET WIRE DAMAGED AT STAPLE 9) STOPPED INSPECTION |