Permit: T05CM01432

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM01432

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/13/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* 1. SUPPORTS FOR M.C CABLE 12" FROM BOXES AND EVERY 4' . ALL RUND LONGER THAN 6" ABOVE DROP CEILING, FOR FIXTURE WHIPS MUST HAVE AT LEAST ONE WORE SUPPORT. WIRES MUST BE TIED TO CEILING GRID. DO NOT USE GRID SUPPORT WIRES. 2. ADD SEISMIC WIRES TO TRACE ( 2 WIRE PER TRAC) ONE WIRE TO EACH FIXTURE OUTLET BOX.