Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/13/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORTS FOR M.C CABLE 12" FROM BOXES AND EVERY 4' . ALL RUND LONGER THAN 6" ABOVE DROP CEILING, FOR FIXTURE WHIPS MUST HAVE AT LEAST ONE WORE SUPPORT. WIRES MUST BE TIED TO CEILING GRID. DO NOT USE GRID SUPPORT WIRES. 2. ADD SEISMIC WIRES TO TRACE ( 2 WIRE PER TRAC) ONE WIRE TO EACH FIXTURE OUTLET BOX. |