Permit: T05CM01412

Parcel: 125076400

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM01412

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) PLUMBING FINAL OK
2) ALL CORRECTIONS MADE OK
3) OK FOR C OF O STOI
09/20/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) INDIRECT WASTE PIPING ALL TO HAVE MINIMUM ONE INCH AIR GAP. MUST BE SUPPORTED, MAY NOT CAUSE SPLASHING
2) ESPRESSO MACHINE INDIRECT WASTE NOT APPROVED
09/15/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE CORRECTIONS FROM 9/14/05 AND COMPLY
2) DO NOT CALL FOR FINAL UNTIL YOU ARE READY
09/14/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE NOTES FOR WH1-NO HEAT TRAPS AND NO INSULATION ON HOT
2) PROVIDE LISTING FOR CUSTARD MACHINE THAT EXEMPTS IT FROM BACKFLOW PROTECTION
3) DRAIN FROM EXPRESSO MACHINE TO BE APPROVED MATERIAL INSTALLED PER 94 UPC FROM POINT OF EXIT FROM DEVICE
4) INSTALL ALL GRATES AND STRAINERS
5) EACH WATER SUPPLIED APPLIANCE TO HAVE IT'S OWN BACKFLOW PROTECTION
6) ICE MACHINE NOT CONNECTED NO BACKFLOW DEVICE
7) OVERHEAD PIPING COVERED WITHOUT INSPECTION-SEE NOTES FROM 7/20/05
8) CONDENSATE HOSE KINKED AT LAVATORY TAIL PIECE