Permit: T05CM01411

Parcel: 13339231A


Addresses:

9616 E QUAIL PL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/13/2007 FRAMING Approved IVRS - Inspection :*
01/17/2007 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING ELECTRIC AND GAS
2) OK TO INSULATE
3) GROUND RODS DRIVEN
4) PER 2003 IRC E3801.10
5) ADD RECEPTACLE BEDROOM HALLWAY
6) GROUND LIGHT BOX IN SECURITY CLOSET
7) PRESSURE TEST OK
8) WHY IS PIPE STUBBED OUT INSIDE L/R WALL ?
01/09/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RED HEAD MISSING NEAR TOILET LAUNDRY
2) CAULK WIRE FOR A/C
3) NO INICATION THAT UFER WAS EVER INSPECTED
4) RECEPTACLE FOR GAS DRYER ?
5) GROUND LIGHT BOX SECURITY CLOSET
6) NEED 1 RECEPTACLE BEDROOM HALLWAY
7) INSTALL VACUUM BREAKERS ON HOSE BIBS
8) PEX MUST BE MINIMUM 12" FROM CAN LIGHTS THRU OUT
9) GAS PIPE IN WALL L/R ?
10) NEED 1" CLEARANCE TO B-VENT
11) FURNACE B-VENT CANNOT RUN HORIZONTAL
12) MINIMUM SLOPE FOR B-VENT IS 30 DEGREE
11/15/2006 FRAMING Not ready for Inspection IVRS - Inspection :*