Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/17/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING ELECTRIC AND GAS 2) OK TO INSULATE 3) GROUND RODS DRIVEN 4) PER 2003 IRC E3801.10 5) ADD RECEPTACLE BEDROOM HALLWAY 6) GROUND LIGHT BOX IN SECURITY CLOSET 7) PRESSURE TEST OK 8) WHY IS PIPE STUBBED OUT INSIDE L/R WALL ? |
|
| 01/09/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RED HEAD MISSING NEAR TOILET LAUNDRY 2) CAULK WIRE FOR A/C 3) NO INICATION THAT UFER WAS EVER INSPECTED 4) RECEPTACLE FOR GAS DRYER ? 5) GROUND LIGHT BOX SECURITY CLOSET 6) NEED 1 RECEPTACLE BEDROOM HALLWAY 7) INSTALL VACUUM BREAKERS ON HOSE BIBS 8) PEX MUST BE MINIMUM 12" FROM CAN LIGHTS THRU OUT 9) GAS PIPE IN WALL L/R ? 10) NEED 1" CLEARANCE TO B-VENT 11) FURNACE B-VENT CANNOT RUN HORIZONTAL 12) MINIMUM SLOPE FOR B-VENT IS 30 DEGREE |
|
| 11/15/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |