Permit: T05CM01408

Parcel: 11202035A


Addresses:

3970 N CAMPBELL AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM01408

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/28/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
NOTE! THIS WORK WAS DONE ABOVE CEILING GRID. SHOULD BE 04036 ABOVE CEILING.
NEC 300.4 CONTROL WIRING ON ROOF. PROTECT IN CONDUIT PROTECT AS NECESSARY
LIQUID LINE - WRAP HEAVY MIL TAPE WHERE COPPER IS IN CONTACT W/STEEL
VERIFY TO AMP FUSES ARE CORRECT FOR CONDENSER.
02/27/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*