Permit: T05CM01408

Parcel: 11202035A


Addresses:

3970 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM01408

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK ELECTRICAL FINAL
02/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
AFTER HOURS INSPECTION
1. SUPPORT FEEDER RACEWAY OFF CEILING GRID AND TIGHTEN ALL SET SCREWS.
2. SUPPORT MC OFF GRID AND INSTALL SLACK WIRES FOR FIXTURES.
3. EQUIPMENT GROUND TO AIR HANDLER IN UNDERSIZED 250.122
4. GROUND AIR HANDLER DISCONNECT
5. USE BUSHING FOR #4 AND LARGER CONDUCTORS
6. RACEWAY TO DISTRIBUTION UNIT NEEDS TO BE STRAPPED AND MECHANICALLY CONTINUOUS.
02/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*HAVE ALL EQUIPMENT OPEN FOR INSPECTION AND HAVE PLANS ON SITE.