Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK ELECTRICAL FINAL |
|
| 02/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* AFTER HOURS INSPECTION 1. SUPPORT FEEDER RACEWAY OFF CEILING GRID AND TIGHTEN ALL SET SCREWS. 2. SUPPORT MC OFF GRID AND INSTALL SLACK WIRES FOR FIXTURES. 3. EQUIPMENT GROUND TO AIR HANDLER IN UNDERSIZED 250.122 4. GROUND AIR HANDLER DISCONNECT 5. USE BUSHING FOR #4 AND LARGER CONDUCTORS 6. RACEWAY TO DISTRIBUTION UNIT NEEDS TO BE STRAPPED AND MECHANICALLY CONTINUOUS. |
|
| 02/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*HAVE ALL EQUIPMENT OPEN FOR INSPECTION AND HAVE PLANS ON SITE. |