Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*CORRECTIONS MADE TO SERVICE ECO | |
| 11/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK CABLE DROP ON NEW SERVICE FOR 480 V | |
| 11/01/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*WIRING CT CAN AND TERMINAL CAN TO BE SECURED AS PER DRAWING IN CANS AS PER UL LISTING 250-92 LAST SECTION STANDARD LOCK NUTS NOT ACCEPTED AS ONLY GROUNDING MEANS AS PER NEC GROUNDING BUSHINGS MUST BE USED WHERE EVER UN PROTECTED CONDUCTORS EXIT OR ENTER EQUIPMENT DIFFERENT SERVICES MUST BE TIED TOGETHER PER NEC. EXISINTING 120/208 V NEW 480 VOLT. ADDRESS NEW SERVICE DRAWING CALLS FOR 1/0 CU GROUND IN EACH PARALLEL RUN DRIVE GRD RODS TO GRADE OR BELOW-REMOVE TRIP HAZARD IN FRONT OF SERVICE SERVICE MUST BE ADDRESSED AS # 2 ALSO ON PERMIT |