Permit: T05CM01408

Parcel: 11202035A


Addresses:

3970 N CAMPBELL AV


Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM01408

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
12/05/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*CORRECTIONS MADE TO SERVICE ECO
11/15/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK CABLE DROP ON NEW SERVICE FOR 480 V
11/01/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*WIRING CT CAN AND TERMINAL CAN TO BE SECURED AS PER DRAWING IN CANS AS PER UL LISTING
250-92 LAST SECTION STANDARD LOCK NUTS NOT ACCEPTED AS ONLY GROUNDING MEANS AS PER NEC GROUNDING BUSHINGS MUST BE USED WHERE EVER UN PROTECTED CONDUCTORS EXIT OR ENTER EQUIPMENT
DIFFERENT SERVICES MUST BE TIED TOGETHER PER NEC. EXISINTING 120/208 V NEW 480 VOLT.
ADDRESS NEW SERVICE
DRAWING CALLS FOR 1/0 CU GROUND IN EACH PARALLEL RUN
DRIVE GRD RODS TO GRADE OR BELOW-REMOVE TRIP HAZARD IN FRONT OF SERVICE
SERVICE MUST BE ADDRESSED AS # 2 ALSO ON PERMIT