Permit: T05CM01403

Parcel: 112040120


Addresses:

2533 E GLENN ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/24/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
08/16/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MECHANICAL LOOKS GOOD. WILL GIVE FINAL WHEN PLUMBING IS FINALED
2) GAS PRESSURE TEST-GARAGE IS SITTING ON 0 PSI. MUST MAINTAIN MINIMUM 10 PSI
05/25/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FURNACE AND WATER HEATER VENT CONNECTORS NOT INSTALLED PROPERLY. ALL JOINTS MUST BE CONNECTED WITH MINIMUM 3 SCREWS AND CRIMPED ENDS TO GO WITH THE AIR FLOW
2) PROVIDE WIRE NUTS ON CONDENSATE PUMP OVERFLOW SENSOR
3) PROVIDE A MINIMUM 1" CLEARANCE FROM COMBUSTIBLES WHERE B-1 VENT PENETRATES THE ROOF
4) PRESSURE GAGE ON GAS LINE IS ON ZERO. PROVIDE MINIMUM 10 POUND TEST