Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
10/24/2005 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
05/09/2005 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) RELIEF COMB. DUCT AT CEILING . NOT SUFFICIENT FREEE AREA. SUGGEST NEW B-1 VENT ABOVE WATER HTR FOR FURN. & WATER HTR. 2) NEED AGA. GAS VALVE AT WATER HTR. 3) NEED TO PRESSURIZE GAS PIPING AT METER LOCATION TO GAS APPLIANCES. FOR MECHANICAL. 1) NOT SUFFICIENT CLEARANCE, FURANCE VENT TO PVC CONDENSATE PIPE. 2) RUN NEW B-1 VENT, CEIL UP THRU ROOF, TERMINATE W/PROPER FLUSHING, STORM COLLAR & CAP. 3) EXPOSED CONTROL WIRING TO SU?? 4) INSULATE ( COMPLETE) REFRIG. LINES AT CONDENSER 5) PLEMIUM DUCT ABOVE COND EVAPORATORS. RESTRICTION TO MUCH SUPPLY AIR. CAN BE OPENED UP FOR MORE AIR FLOW.