Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK FOR FINAL SHELL ONLY |
|
| 10/21/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*DUCT INSULATION INSIDE BLDG. DOES NOT MEET MIN R5. 5" LINER IS R4.2 & 1 1/2" FOIL WRAP IS R4.2. SEE 2000 I.E.C.C CONDENSATE DRAINS ARE OK PROVIDE BACKING AROUND CEILING BOXES.INSTALL EXHAUST FANS. RECALL FOR INSPECTION. |