Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/01/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) OK FOR FINAL SHELL ONLY
10/21/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*DUCT INSULATION INSIDE BLDG. DOES NOT MEET MIN R5. 5" LINER IS R4.2 & 1 1/2" FOIL WRAP IS R4.2. SEE 2000 I.E.C.C
CONDENSATE DRAINS ARE OK
PROVIDE BACKING AROUND CEILING BOXES.INSTALL EXHAUST FANS. RECALL FOR INSPECTION.