Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM01374
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/17/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* TO GENL. CONTRACTOR. IF THE N EXTERIOR EMERGENCY REMOTE HEAD, ETC. LITE FIXTURES ARE NOT GOING TO BE INSTALLED, THEN, PLEASE HAVE THE ENGINEER OF RECORD( CHAS. A GIROUD) ISSUE HIS LETTER EXPRESSING HIS CONSENT. THANK YOU. RECALL WHEN ENGINEERS LETTER IS ON SITE. | |
| 05/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED EMERGENCY AND EXIT LIGHTING TO BE OPERABLE. INSTALL EXTERIOR EMERGENCY 'N' LITES PER PLAN. INSTALL EMERGENCY BATTERY PAK-IN FIXTURE DESIGNATED ON PLAN |
|
| 05/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The fixtures are not per plans and specifications.| 250* ALL RELOCATED 2 X4 DROP IN FIXTURES MUST: 1. HAVE SEISMIC WIRES INSTALLED ( 2 CADDY CORNER) 2. BE MECHANICALLY FASTENED TO CEILING GRID. EG- SCREWED TO MAIN RUNNER T-CENTER OF FIXTURE-2 ENDS, OR -USE APPROVED CLIPS. RECALL, WHEN DONE. |