Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM01364
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. PLUMBING FINAL OK OK FOR LETTER OF COMPLETION S.T.O.I |
|
01/31/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OVERHEAD COPPER OK CLOSET FLANGES OK OK TO COVER ALL AREAS |
|
01/19/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. MAKE SURE YOUR TRUCKS DO NOT BLOCK EGRESS THRU THE PARKING LOT. 2. CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS. |
|
12/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | 1. IS 5 2003 UPC NO FEMALE ABS THREADS IN INACCESSIBLE LOCATION -- REMOVE BLAKE TEE. 2. NEED TO SEE CLOSET FLANGE UNIT #1 |
|
12/13/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NOTE #1: HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP. NOTE #2: DO NOT USE RECTOR SEAL ON ABS!!! |
|
12/02/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNITS #4 & #5 OK TO COVER WALLS |
|
10/30/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. UNIT #10 & #11 CORRECTIONS MADE OK OK TO COVER 2. CLOSET FLANGES TO BE SCREWED TO THE FLOOR |
|
10/26/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT 10 & 11 PROVIDE CORRECT SLOPE ON VENT AND VENT FITTINGS. 1 1/2" TRAP ARM REQUIRED FOR LAVS I BELIEVE THAT A TEST ON EVERY JOINT IS NECESSARY ON THIS JOB. FILL ENTIRE SYSTEM. |
|
10/25/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/20/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT #1 WIER OF TRAP SHALL NOT BE ABOVE POINT OF VENT. LAV TRAP ARM SHALL BE 1 1/2" CLEANOUT SHALL BE ACCESSIBLE. CHECK YOUR WATER SUPPLY STUB OUT LOCATION FOR WC UNIT #10 DOUBLE FIXTURE FITTING REQUIRED AT DOUBLE FIXTURE CONNECTION. REVENT ABOVE 42" INSTALL SAFETY PLATES INSTALL SAN T AT REVENT IN PROPER DIRECTION OF PLAN CLEAN OUT SHALL BE ACCESSIBLE SUPPORT OVERHEAD COPPER AT CHANGE OF ELEVATION |
|
09/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. COPPER SUPPLY OVERHEAD FOR EASTSIDE COMPLETE. 2. UNIT 12 OK TO COVER WALLS. |
|
09/01/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. UNIT #2 & #3 ABS THRU ROOF OK COPPER OK OK TO COVER WALLS NEED TO SEE CLOSET FLANGES |
|
08/31/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT HORIZONTAL OVERHEAD PIPE 2. FILL ABS SYSTEM WITH WATER 3. NEED TO SEE CLOSET FLANGES |
|
07/13/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | 1. EAST UNIT PLUMBING WALL OK TO COVER. NO TEST ON ABS SUPPORT VERTICAL ABS NEED TO SEE CLOSET FLANGE |
|
07/10/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. EAST UNIT, PLUMBING WALL, OK TO COVER TO OVERHEAD |
|
01/23/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO POUR NEXT SECTION |