Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUND 45 BOXES PROPERLY 2. BOND OR GROUND BAR IN 24 X 24 J-BOX NOT SECURED PROPERLY - NO SHEETMETAL SCREWS 3. #10 BRANCH CIRCUITING OK FOR DERATING 4. SUPPORT MC CABLE PER CODE CABLING NOT ALLOWED TO BE BUNDLED OVER 24" IN LENGTH 5. OK OUTDOOR LTG 6. SUPPORT EMT PER CODE |