Permit: T05CM01364

Parcel: 10406011E


Addresses:

2075 W GARDNER LN


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM01364

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GROUND 45 BOXES PROPERLY
2. BOND OR GROUND BAR IN 24 X 24
J-BOX NOT SECURED PROPERLY - NO SHEETMETAL SCREWS
3. #10 BRANCH CIRCUITING OK FOR DERATING
4. SUPPORT MC CABLE PER CODE CABLING NOT ALLOWED TO BE BUNDLED OVER 24" IN LENGTH
5. OK OUTDOOR LTG
6. SUPPORT EMT PER CODE