Permit: T05CM01364

Parcel: 10406011E


Addresses:

2075 W GARDNER LN


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T05CM01364

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2007 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
01/29/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
INSPECTION FOR SERVICE AND ALL SUB-PANELS AND FEEDERS
I RECEIVED TEST REPORTS FROM ELECTRICAL RELIABILITY SERVICES TODAY. I WILL REVIEW THEM IN THE OFFICE AND LET YOU KNOW THE RESULTS (OK/NOT OK) CUTTER
241-5017, 444-6290
FEEDER/SUB-PANEL INSPECTION
1. SELF TAP SCREWS NOT ALLOWED FOR GROUNDING CONNECTION -- NEC 250.8
2. INSTALL COMPLETE UNIT NUMBERS
3. GROUND PANEL ENCLOSURES -- NEC 408.20
4. BRANCH CKTS TO BE DERATED - NEC 310.15 B 2
5. SEAL UNUSED OPENING IN J-BOX - NEC 314.17A
01/19/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
12/15/2006 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/14/2006 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
The service is not per code.| 210*