Permit: T05CM01364

Parcel: 10406011E


Addresses:

2075 W GARDNER LN

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/12/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :$
1) CHECK FOR FOLLOWING ITEMS: INSULATION UNDER GROUND TERMINATIONS, TIGHTEN CONNECTION LOOSE/STRIPPED GROUND SCREWS IN PANELS, J-BOXES BRANCH CIRCUIT CONDUCTORS TO BE PROPERLY DERATED, NEC 310.15
12/15/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/11/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection 1. NEED TO HAVE U.L RE-CERTIFY SERVICE, THEN CALL FOR INSPECTION (SPOKE TO NIGOR BY PHONE)
11/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INTERIOR WALLS OK
10/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ENTRY AREA WALL COVER UNITS #10 & #11
10/11/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNIT 13 WALL & HARD LID COVER
RECEPTION, BATH AREA
10/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER IN WALL BETWEEN UNITS #9 & #10
09/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNIT 12 COVER
NO MORE DRYWALL BEFORE INSPECTIONS.
08/23/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL WALL/HARD LID COVER
UNITS 2 & 3 FRONT ENTRY & BATH AREAS
08/22/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
07/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PARTIAL OK OFFICES & BATHROOM
FROM NOW ON USE PROPER STRAPS FOR MC & EMT
TIE WIRE WILL NO LONGER BE APPROVED.
07/10/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. FINISH AC CIRCUITS ADD BOXES
2. MISSING PHONE CIRCUITS & BOXES
3. MISSING TELEPHONE RECEPT. & GROUND
4. MISSING WAREHOUSE OUTLETS
5. FINISH MC CABLES ABOVE BATHROOM CEILING & J-BOX
6. WHAT IS 2-GANG BOX FOR ABOVE SWITCH IN BATHROOM.