Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 09/08/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SECONDARY DITCH COVER NOTE: UFER CUT |
|
| 08/22/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* UNIT 2 & 3 ROUGH OK TO COVER SUBPANEL RACEWAY TRENCH 1. USE PROPER CRIMP TOOL FOR GROUND CRIMP SLEEVES NEC 110.3, ETC. 2. PROVIDE ADDITIONAL BACK SUPPORT FOR BOXES WITH MC TO KEEP FROM ROLLING IN WALL -- NEC 314.23 3. EQUIPMENT GROUND ON BOXES NEEDS TO BE TIGHT UNDER SCREW. |
|
| 08/18/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK TO COVER 13-2" PVC FEEDERS FOR J-BOXES REAR OF UNITS TO WEST END OF BLDG |