Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM01340
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) NONE OF RECORD STEVE JACOBS AND H. PEDROZA TESTED THE ARC FAULTS NEAUTRALS TRIPPED. RESIET ARC FAULTS AT PANEL, TRUE READING |
|
08/30/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST TENSION TAG MISSING 2) PAINT PVC LINES 3) NO POWER TO EXTERIOR GFCI, FRONT GFCI BURIED IN WALL 4) COACH LIGHT AT GARAGE NO SHEETHING INTO ELEC BOX, MIN 1/4" REQUIRED 5) SERVICE OUTLET ROMIEX? IN ATTIC TIGHT AND MOVE AWAY FROM ATTIC ACCESS 6) FAV SRC PAN FULL OF CONSTRUCTION DIEBDI? 7) ARC FAULT TESTER SHOWS SHARED NEUTRALS |
|
08/29/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/26/2005 | BUILDING - FINAL | Cancelled | CANCELLED PER PAPERWORK TURNED IN BY INSPECTOR F. GREER |